A1N 125 TMF 80-800 3p F F
Product ID:71186
Updated: 2026/4/5

Key Features
- 1Ensure reliable operation under heavy loads with a 36 kA short-circuit breaking capacity. 2、Meet EU RoHS and REACH standards for environmental compliance and safety. 3、Benefit from precise protection with integrated thermal and magnetic release mechanisms. 4、Simplify installation and maintenance using front terminal connections. 5、Utilize across diverse applications with a wide 240-500V AC and 250V DC range.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 1SDL000183R0001 9AKK108467A6707 | Product Net Width | 76.2 mm |
| Product Net Height | 130 mm | Product Net Depth / Length | 60 mm |
| Product Net Weight | 0.798 kg | Product Main Type | SACE FORMULA |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Version | F | Electrical Durability | 1500 cycle |
| Mechanical Durability | Nr. Operations 8500 cycle | Number of Poles | 3P |
| Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Power Loss | at Rated Operating Conditions per Pole 9 W |
| Rated Current (In) | Main Circuit 80 A | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Rated Insulation Voltage (Ui) | 690 V | Rated Operational Voltage | 550 V AC 250 V DC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (240 V AC) 50 kA (380 V AC) 18 kA (415 V AC) 7.5 kA (440 V AC) 6.25 kA (480 V AC) 4.5 kA (500 V AC) 2.5 kA (250 V DC) 2 Poles in Series 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 100 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (480 V AC) 18 kA (500 V AC) 10 kA (250 V DC) 10 kA |
| Rated Uninterrupted Current (Iu) | 125 A | Release | TMF |
| Release Type | TM | Short-Circuit Performance Level | N |
| Standards | IEC | Sub-type | A1 |
| Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
| Manufacturer ID | 1SDA066729R1 |
Specifications may be subject to change without notice