ACS800-01-0070-5
Product ID:93238
Updated: 2026/4/3

Key Features
- 1Integrate a built-in choke for harmonic filtering and drive protection. 2、Utilize flexible, programmable I/O with galvanically isolated inputs. 3、Deploy the IP21-rated, compact design in harsh industrial environments. 4、Operate via an alphanumeric, multilingual control panel with startup assistant. 5、Achieve 98% efficiency at nominal power to reduce energy costs.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Weight | 34 kg | Product Net Depth / Length | 286 mm |
| Product Net Height | 739 mm | Product Net Width | 265 mm |
| Package Level 1 Units | 1 carton | Number of Phases | 3 |
| Frequency (f) | 48 ... 63 Hz | Frame Size | R5 |
| Input Voltage (Uin) | 380 ... 500 V | Mounting Type | Wall-mounting |
| Output Current, Heavy-Duty Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">IHD</span>) | 69 A | Output Current, Light-Overload Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">ILD</span>) | 88 A |
| Output Current, Normal Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">In</span>) | 96 A | Output Power, Heavy-Duty Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">PHD</span>) | 45 kW |
| Output Power, Light-Overload Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">PLD</span>) | 55 kW | Output Power, Normal Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">Pn</span>) | 55 kW |
| Apparent Power Output | 83 kV·A | Efficiency Level | IE2 |
| Standby Loss | 77 W | Temperature Rating | Maximum 50 °C |
| UNSPSC | 26101751 39122001 | SCIP | 9137de42-9806-4708-a144-33d9e4e244e2 Finland (FI) |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) | Product Name | Frequency Converter |
| Manufacturer ID | 64576585 |
Specifications may be subject to change without notice