ACS880-17-0320A-7
Product ID:70975
Updated: 2026/4/3

Key Features
- 1Achieve precise speed and torque control with ABB's DTC technology. 2、Ensure durability in harsh conditions with coated boards. 3、Power applications from 0.55 to 6000 kW for versatility. 4、Integrate safe torque off (STO) as a standard safety feature. 5、Simplify setup using a removable memory unit and friendly interface.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Weight | 1180 kg 2601 lb | Product Net Depth / Length | 698 mm 27.480 in |
| Product Net Height | 2145 mm 84.449 in | Product Net Width | 1230 mm 48.425 in |
| Package Level 1 Depth / Length | 1100 mm 43.307 in | Package Level 1 Height | 2373 mm 93.425 in |
| Package Level 1 Width | 1444 mm 56.850 in | Number of Phases | 3 |
| Degree of Protection | IP22 | Enclosure Type NEMA | Type1 |
| Altitude | 1000 m | Operating Humidity (RH<span style="font-size:x-small;">amb</span>) | 5 ... 95 |
| Power Factor | 1 | Sound dB (A) | 75 dB(A) |
| Multiple Battery Information | Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g | Frequency (f) | 48 ... 63 Hz |
| Frame Size | R8i+R8i | Input Voltage (Uin) | 525 ... 690 V |
| Communication Protocol | CAN DeviceNet EtherNet/IP MODBUS Other Bus Systems PROFIsafe PROFIBUS PROFINET IO TCP/IP | Number of Hardware Interfaces | Industrial Ethernet 0 Parallel 0 PROFINET 0 RS-232 0 RS-422 0 RS-485 1 Serial TTY 0 USB 1 |
| Includes | Control unit PC connection | Analog Inputs | 4 |
| Analog Outputs | 4 | Number of Digital In/Outputs | 14 / 10 |
| Output Current, Heavy-Duty Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">IHD</span>) | 239 A | Output Current, Light-Overload Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">ILD</span>) | 307 A |
| Output Current, Normal Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">In</span>) | 320 A | Output Power, Heavy-Duty Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">PHD</span>) | 200 kW |
| Output Power, Light-Overload Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">PLD</span>) | 250 kW | Output Power, Normal Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">Pn</span>) | 315 kW |
| Ecodesign Exemption | Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c). | Output Current, Heavy-Duty Use (UL) | 239 A |
| Output Current, Light-Overload Use (UL) | 307 A | Output Current, Normal Use (UL) | 320 A |
| Output Power, Heavy-Duty Use (UL) | 250 Hp | Output Power, Light-Overload Use (UL) | 300 Hp |
| Output Power, Normal Use (UL) | 350 Hp | UNSPSC | 39122001 |
| SCIP | 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland (FI) | WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| Product Name | Frequency converter | Manufacturer ID | 3AXD50000145874 |
Specifications may be subject to change without notice