ACS880-17-1980A-5
Product ID:90976
Updated: 2026/4/3

Key Features
- 1Achieve precise speed and torque control with Direct Torque Control (DTC). 2、Save up to 30% energy via the built-in energy optimizer. 3、Ensure reliability in harsh environments with coated PCBs and IP55 rating. 4、Connect seamlessly to all major automation networks for remote monitoring. 5、Customize the drive for your specific application and industry needs.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Weight | 2930 kg 6460 lb | Product Net Depth / Length | 738 mm 29.055 in |
| Product Net Height | 2145 mm 84.449 in | Product Net Width | 3230 mm 127.165 in |
| Package Level 1 Depth / Length | 1100 mm 43.307 in | Package Level 1 Height | 2376 mm 93.543 in |
| Package Level 1 Width | 3944 mm 155.276 in | Number of Phases | 3 |
| Degree of Protection | IP22 | Enclosure Type NEMA | Type1 |
| Altitude | 1000 m | Operating Humidity (RH<span style="font-size:x-small;">amb</span>) | 5 ... 95 |
| Power Factor | 1 | Sound dB (A) | 78 dB(A) |
| Multiple Battery Information | Lithium Coin, BR2032, 2pcs, 3V, 200mAh, 3g | Frequency (f) | 48 ... 63 Hz |
| Frame Size | 3xR8i+3xR8i | Input Voltage (Uin) | 380 ... 500 V |
| Communication Protocol | CAN DeviceNet EtherNet/IP MODBUS Other Bus Systems PROFIsafe PROFIBUS PROFINET IO TCP/IP | Number of Hardware Interfaces | Industrial Ethernet 0 Parallel 0 PROFINET 0 RS-232 0 RS-422 0 RS-485 1 Serial TTY 0 USB 1 |
| Includes | Control unit PC connection | Analog Inputs | 4 |
| Analog Outputs | 4 | Number of Digital In/Outputs | 14 / 10 |
| Output Current, Heavy-Duty Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">IHD</span>) | 1481 A | Output Current, Light-Overload Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">ILD</span>) | 1901 A |
| Output Current, Normal Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">In</span>) | 1980 A | Output Power, Heavy-Duty Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">PHD</span>) | 1000 kW |
| Output Power, Light-Overload Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">PLD</span>) | 1300 kW | Output Power, Normal Use (<span style="font-size:11.0pt;font-family:'Calibri',sans-serif;">Pn</span>) | 1400 kW |
| Ecodesign Exemption | Energy efficiency data is not provided for the drive. The regenerative drives are exempt from the EU ecodesign requirements (Regulation EU/2019/1781, §2.3.c). | Output Current, Heavy-Duty Use (UL) | 1481 A |
| Output Current, Light-Overload Use (UL) | 1901 A | Output Current, Normal Use (UL) | 1980 A |
| Output Power, Heavy-Duty Use (UL) | 1250 Hp | Output Power, Light-Overload Use (UL) | 1500 Hp |
| Output Power, Normal Use (UL) | 1750 Hp | UNSPSC | 39122001 |
| SCIP | 944D8A5E-036D-404E-9036-0D3C1EA703AD Finland (FI) | WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| Product Name | Frequency converter | Manufacturer ID | 3AXD50000145850 |
Specifications may be subject to change without notice