AF116-30-11B-33
Product ID:85208
Updated: 2026/4/6

Key Features
- 1Operate from 100-250 V, 50/60 Hz AC/DC for flexibility. 2、Utilize AF technology to reduce panel energy consumption. 3、Integrate surge protection for reliable operation. 4、Suit motor starting and distribution up to 690 V. 5、Extend easily with auxiliary contact blocks.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 90 mm | Product Net Depth / Length | 142.5 mm |
| Product Net Height | 150 mm | Product Net Weight | 1.3 kg |
| Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 1 |
| Rated Operational Voltage | Main Circuit 690 V | Rated Frequency (f) | Main Circuit 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 160 A | Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 160 A (690 V) 60 °C 145 A (690 V) 70 °C 130 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 116 A (440 V) 55 °C 116 A (500 V) 55 °C 110 A (690 V) 55 °C 65 A (380 / 400 V) 55 °C 116 A (220 / 230 / 240 V) 55 °C 116 A | Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 116 A (440 V) 60 °C 116 A (500 V) 60 °C 110 A (690 V) 60 °C 65 A (380 / 400 V) 60 °C 116 A (220 / 230 / 240 V) 60 °C 116 A |
| Rated Operational Power AC-3 (Pe) | (415 V) 55 kW (440 V) 75 kW (500 V) 75 kW (690 V) 55 kW (380 / 400 V) 55 kW (220 / 230 / 240 V) 30 kW | Rated Operational Power AC-3e (Pe) | (415 V) 55 kW (440 V) 75 kW (500 V) 75 kW (690 V) 55 kW (380 / 400 V) 55 kW (220 / 230 / 240 V) 30 kW |
| Rated Breaking Capacity AC-3 | 8 x Ie AC-3 | Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 | Rated Making Capacity AC-3e | 12 x Ie AC-3e |
| Short-Circuit Protective Devices | gG Type Fuses 250 A | Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour | Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour | Coil Operating Limits | (acc. to IEC 60947-4-1) Uc (at θ ⤠70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V | Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A Pull-in at Max. Rated Control Circuit Voltage DC 135 W |
| Operate Time | Between Coil De-energization and NO Contact Opening 37 ... 47 ms Between Coil Energization and NO Contact Closing 25 ... 55 ms | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 |
| Terminal Type | Main Circuit: Bars | General Use Rating UL/CSA | (600 V AC) 160 A |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 15 Hp (200 V AC) Three Phase 30 hp (208 V AC) Three Phase 30 hp (220 ... 240 V AC) Three Phase 20 Hp (220 ... 240 V AC) Three Phase 40 hp (440 ... 480 V AC) Three Phase 40 Hp (440 ... 480 V AC) Three Phase 75 hp (550 ... 600 V AC) Three Phase 50 Hp (550 ... 600 V AC) Three Phase 100 hp | Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C |
| Maximum Operating Altitude Permissible | Without Derating 3000 m | Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching | ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching | eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 | IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
| E-Number (Sweden) | 3210529 | Manufacturer ID | 1SFL427002R3311 |
Specifications may be subject to change without notice