DS201 B10 A30 UL

Product ID:80780
Updated: 2026/4/4
ABB DS201 B10 A30 UL

Key Features

  • 1Safeguard circuits with advanced overcurrent and short-circuit protection. 2、Provide comprehensive protection against sinusoidal AC and pulsating DC earth faults. 3、Detect residual currents as low as 30 mA for enhanced personnel safety. 4、Ensure durability with 20,000 electrical cycles meeting IEC 61009-1. 5、Simplify integration via DIN rail mounting for quick installation.
Product Details
DS201 B10 A30 UL
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Standards
IEC 61009-1 IEC 61009-2-1 UL 1053 UL 1077 CSA C22.2 N0. 235
Tripping Characteristic
B
Type of Residual Current
Type A
Rated Operational Voltage
acc. to IEC 60898-1 240 V
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 500 V
Test Voltage (Ut)
110…277 V
Rated Impulse Withstand Voltage (Uimp)
4 kV
Dielectric Test Voltage
2 kV
Rated Current Sensitivity
0.03 A
Rated Current (In)
10 A
Rated Residual Current
30 mA
Rated Short-Circuit Capacity
6 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
6 kA
Rated Service Short-Circuit Breaking Capacity (Ics)
7.5 kA
Rated Frequency (f)
50 … 60 Hz
Power Loss
Average per Pole 1.2 W Phase Pole 1.8 W Neutral Pole 0.5 W Total 2.3 W
Power Supply Connection
Arbitrary
Contact Position Indication
Red ON / Green OFF
Energy Limiting Class
3
Electrical Endurance
10000 cycle
Mechanical Endurance
20000 cycle
Number of Protected Poles
1
Number of Poles
2
Number of Modular Spacings per DIN Rail
2
Fault Indication
Blue flag on toggle
Operating Characteristic
Instantaneous
Overvoltage Category
III
Position of Neutral Terminals
Right
Tightening Torque
2.8 N·m
Accessory Type
Auxiliary contact, Signal contact / auxiliary contact, Shunt trip, Auxiliary contact for bottom fitting, Overvoltage release, Motor operating device
Mounting Type
DIN-Rail
Screw Terminal Type
Failsafe Bi-directional Cylinder-lift Terminal
Mounting Position
Any
Accessories Available
Yes
Connecting Capacity
Busbar 10 ... 10 mm² Rigid 25 ... 25 mm² Flexible 25 ... 25 mm²
Wire Stripping Length
12 mm
Terminal Type
Screw Terminals
Ambient Air Temperature
Operation -25 … 55 °C
Reference Ambient Air Temperature
30 °C
Degree of Protection
IP20 IP40
Pollution Degree
2
Environmental Conditions
28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 %
Resistance to Vibrations
20 Cycles with Load 0.8 In: 1g or 1mm 50 … 150 … 5 Hz
Resistance to Shock acc. to IEC 60068-2-27
25g 2 shocks 13 ms
Width in Number of Modular Spacings
2
Product Net Width
35 mm
Product Net Height
85 mm
Product Net Depth / Length
69 mm
Product Net Weight
200 g
Built-In Depth (t2)
69 mm
ETIM 8
EC000905 - Earth leakage circuit breaker
ETIM 9
EC000905 - Earth leakage circuit breaker
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B
Business To Consumer
CN8
85363010
eClass
V11.0 : 27142207
Object Classification Code
Q
Manufacturer ID
2CSR255187R1105

Specifications may be subject to change without notice