LS33P52B11

Product ID:75977
Updated: 2026/4/3
ABB LS33P52B11

Key Features

  • 1Withstand harsh environments using durable fiber-glass reinforced UL-V0 material. 2、Ensure precise actuation with an adjustable rubber roller lever (Ø50 mm). 3、Guarantee reliable switching via snap action contacts (1 N.O + 1 N.C). 4、Simplify installation with an ISO M20x1.5 cable entry. 5、Save panel space with compact 50x126.5x52 mm dimensions.
Product Details
LS33P52B11
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
50 mm
Product Net Height
126.5 mm
Product Net Depth / Length
52 mm
Product Net Weight
0.107 kg
Action Type of the Contact Element (acc. to IEC 60947-5-1)
Snap Action Simultaneous
Actuator Type
adjustable rubber roller lever (Ø50 mm)
B10d Value
Operations 30 Millions
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-5-1, Θ = 40 °C 10 A
Degree of Protection
acc. to IEC 60529 IP65
Housing Material
Plastic
Maximum Electrical Switching Frequency
(AC-15) 3600 cycles per hour (DC-13) 3600 cycles per hour
Maximum Mounted Auxiliary Contacts
1 NO, 1 NC
Mechanical Durability
10 million
Mounting Type
30 mm (EN 50047)
Number and Type of Bottom Cable Glands
1 x M20x1.5 - Bottom
Pilot Duty UL/CSA
A600 Q600
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Operational Current AC-15 (Ie)
(230 V AC) 3.1 A (400 V) NC 4 (24 V) 10 A (130 V) 5.5 A (240 V) 3 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 500 V acc. to UL/CSA 600 V
Rated Operational Current DC-13 (Ie)
(24 V) 6 A (110 V) 0.6 A (125 V) 0.55 A (250 V) 0.4 A
Short-Circuit Protective Devices
gG Type Fuses 10 A
Ambient Air Temperature
Operation -25 ... +70 °C Storage -30 ... +80 °C
Object Classification Code
B
ETIM 6
EC000030 - End switch
ETIM 7
EC000030 - End switch
ETIM 8
EC000030 - End switch
eClass
V11.0 : 27272601
UNSPSC
39121500
Manufacturer ID
1SBV012252R1211

Specifications may be subject to change without notice