MS132-10KT

Product ID:82917
Updated: 2026/4/3
ABB MS132-10KT

Key Features

  • 1Safely disconnect motors with a single action. 2、Ensure reliable operation across various temperatures. 3、Prevent accidental tripping during operation. 4、Use easily with clear switch position indication. 5、Protect against short circuits up to 100 kA.
Product Details
MS132-10KT
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Net Width
45 mm
Product Net Height
112 mm
Product Net Depth / Length
87 mm
Product Net Weight
0.296 kg
Rated Service Short-Circuit Breaking Capacity (Ics)
(230 V AC) 100 kA (400 V AC) 100 kA (440 V AC) 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)
200 A
Setting Range
6.3 ... 10 A
Rated Operational Voltage
Main Circuit 690 V AC
Rated Operational Current (Ie)
10 A
Rated Frequency (f)
Main Circuit 50 Hz Main Circuit 60 Hz
Operating Frequency (fsw)
0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 6 kV
Rated Insulation Voltage (Ui)
690 V
Power Loss
at Rated Operating Conditions per Pole 0.7 ... 1.7 W
Number of Poles
3P
Conventional Free-air Thermal Current (Ith)
Main Circuit 10 A
Degree of Protection
Housing IP20 Main Circuit Terminals IP20
Pollution Degree
3
Electrical Durability
50000 cycle
Mechanical Durability
100000 cycle
Terminal Type
Push-in Spring Terminals
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x 0.5 ... 4 mm² Flexible with Insulated Ferrule 1x 0.5 ... 4 mm² Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm² Flexible 1/2x 0.75 ... 4 mm² Solid 1/2x 1 ... 2.5 mm² Stranded 1/2x 1 ... 6 mm²
Wire Stripping Length
Main Circuit 12 mm
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance
Electrical Conductive Board, Vertical 75 mm Other Device Same Type, Horizontal 9 mm Other Device Same Type, Vertical 150 mm
Actuator Type
Rotary Handle
Contact Position Indication
ON / OFF / TRIP
Standards
IEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 IEC 60335-2-40 A2L
Short-Circuit Current Rating (SCCR)
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
Maximum Operating Voltage UL/CSA
Main Circuit 600 V AC
Horsepower Rating UL/CSA
(120 V AC) Single Phase 0.5 Hp (220 ... 240 V AC) Single Phase 1.5 Hp
Full Load Amps Motor Use
(120 V AC) Single Phase 9.8 A (220 ... 240 V AC) Single Phase 10 A
Locked Rotor Amps
(120 V AC) Single Phase 58.8 A (220 ... 240 V AC) Single Phase 58.8 A
Connecting Capacity Main Circuit UL/CSA
Stranded 1/2x 18-10 AWG Stranded 1x 8 AWG
Ambient Air Temperature
Around the Enclosure 0 ... +40 °C Operation -25 ... +70 °C Operation Compensated -25 ... +60 °C Storage -50 ... +80 °C
Ambient Air Temperature Compensation
Yes
Maximum Operating Altitude Permissible
2000 m
Resistance to Shock acc. to IEC 60068-2-27
11 ms Pulse 25g
Resistance to Vibrations
5g 3 ... 150 Hz
Object Classification Code
F
ETIM 5
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 6
EC000228 - Power circuit-breaker for trafo/generator/installation prot.
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
eClass
V11.0 : 27370409
UNSPSC
39121601
IDEA Granular Category Code (IGCC)
4813 >> Circuit breakers
E-Number (Finland)
3709087
Manufacturer ID
1SAM340010R1010

Specifications may be subject to change without notice