MS132-6.3KT
Product ID:85766
Updated: 2026/4/3

Key Features
- 1Safeguard motors from short circuits, overloads, and phase failures. 2、Operate easily with a rotary handle for ON/OFF/Trip actions. 3、Install in tight spaces with compact 90x45x86.8 mm dimensions. 4、Adjust the current setting for precise overload protection. 5、Use safely in hazardous areas with ATEX approval.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 45 mm | Product Net Height | 112 mm |
| Product Net Depth / Length | 87 mm | Product Net Weight | 0.289 kg |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 100 kA (400 V AC) 100 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (400 V AC) 100 kA |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 126 A | Setting Range | 4.0 ... 6.3 A |
| Rated Operational Voltage | Main Circuit 690 V AC | Rated Operational Current (Ie) | 6.3 A |
| Rated Frequency (f) | Main Circuit 50 Hz Main Circuit 60 Hz | Operating Frequency (fsw) | 0 ... 400 Hz |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV | Rated Insulation Voltage (Ui) | 690 V |
| Power Loss | at Rated Operating Conditions per Pole 0.7 ... 1.8 W | Number of Poles | 3P |
| Conventional Free-air Thermal Current (Ith) | Main Circuit 6.3 A | Degree of Protection | Housing IP20 Main Circuit Terminals IP20 |
| Pollution Degree | 3 | Electrical Durability | 50000 cycle |
| Mechanical Durability | 100000 cycle | Terminal Type | Push-in Spring Terminals |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.5 ... 4 mm² Flexible with Insulated Ferrule 1x 0.5 ... 4 mm² Flexible with Insulated Ferrule 2x 0.5 ... 2.5 mm² Flexible 1/2x 0.75 ... 4 mm² Solid 1/2x 1 ... 2.5 mm² Stranded 1/2x 1 ... 6 mm² | Wire Stripping Length | Main Circuit 12 mm |
| Mounting Position | 1 ... 6 | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Minimum Mounting Distance | Electrical Conductive Board, Vertical 75 mm Other Device Same Type, Horizontal 9 mm Other Device Same Type, Vertical 150 mm | Actuator Type | Rotary Handle |
| Contact Position Indication | ON / OFF / TRIP | Standards | IEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 IEC 60335-2-40 A2L |
| Short-Circuit Current Rating (SCCR) | Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kA Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA | Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 0.25 Hp (220 ... 240 V AC) Single Phase 0.5 Hp | Full Load Amps Motor Use | (120 V AC) Single Phase 6.3 A (220 ... 240 V AC) Single Phase 6.3 A |
| Locked Rotor Amps | (120 V AC) Single Phase 37.8 A (220 ... 240 V AC) Single Phase 37.8 A | Connecting Capacity Main Circuit UL/CSA | Stranded 1/2x 18-10 AWG Stranded 1x 8 AWG |
| Ambient Air Temperature | Around the Enclosure 0 ... +40 °C Operation -25 ... +70 °C Operation Compensated -25 ... +60 °C Storage -50 ... +80 °C | Ambient Air Temperature Compensation | Yes |
| Maximum Operating Altitude Permissible | 2000 m | Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g |
| Resistance to Vibrations | 5g 3 ... 150 Hz | Object Classification Code | F |
| ETIM 5 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. | ETIM 6 | EC000228 - Power circuit-breaker for trafo/generator/installation prot. |
| ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| eClass | V11.0 : 27370409 | UNSPSC | 39121601 |
| IDEA Granular Category Code (IGCC) | 4813 >> Circuit breakers | E-Number (Finland) | 3709086 |
| Manufacturer ID | 1SAM340010R1009 |
Specifications may be subject to change without notice