- 1Ensure high reliability for consistent industrial performance. 2、Operate across 50Hz and 60Hz frequencies for versatile applications. 3、Install the compact 74mm block design to save panel space. 4、Choose front or side mounting for flexible setup options. 5、Meet IEC 60947-5-1 and VDE 0110 standards for compliance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Width | 44 mm | Product Net Depth / Length | 74 mm |
| Product Net Height | 74 mm | Product Net Weight | 0.315 kg |
| Number of Auxiliary Contacts NO | 4 | Number of Auxiliary Contacts NC | 0 |
| Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V | Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Π= 40 °C 16 A | Rated Operational Current AC-15 (Ie) | (500 V) NC 2 (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A (400 / 440 V) 2 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A for 1 s 100 A | Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour (DC-13) 900 cycles per hour |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.30 A / 66 W (250 V) 0.30 A / 75 W (400 V) 2.8 A / 134 W (500 V) 1 A / 72 W | Rated Insulation Voltage (Ui) | acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV | Maximum Mechanical Switching Frequency | 6000 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 380 ... 400 V 60 Hz 400 ... 415 V | Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 16 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NC Contact Opening 7 ... 21 ms Between Coil Energization and NO Contact Closing 10 ... 26 ms |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | Terminal Type | Screw Terminals |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb Control Circuit 9 in·lb | Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C |
| Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II | Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Object Classification Code | K | ETIM 7 | EC000196 - Contactor relay |
| ETIM 8 | EC000196 - Contactor relay | ETIM 9 | EC000196 - Contactor relay |
| eClass | V11.0 : 27371001 | UNSPSC | 39121500 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors | Manufacturer ID | 1SBH901074R8540 |