OS250D12M1P

Product ID:74988
Updated: 2026/7/14
ABB OS250D12M1P

Key Features

  • 1Deliver high performance with a 250 A rated permanent current.
  • 2Ensure reliable operation at a maximum voltage of 1000 V.
  • 3Provide robust protection with an 80 kA rated short-circuit current.
  • 4Simplify installation via busbar mounting and connector compatibility.
  • 5Meet strict safety standards with essential industrial certifications.

Need price and lead time?

Request a quote for original ABB OS250D12M1P. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Pollution Degree
3
Product Net Width
206 mm
Product Net Height
199 mm
Product Net Depth / Length
154 mm
Product Net Weight
3.6 kg 7.9 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Fuse Size
NH0 NH1
Fuse System
DIN
Handle Type
Handle and shaft included
Mounting Type
Base mounting
Number of Poles
3
Operating Mode
Front Operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 13 W
Rated Conditional Short-Circuit Current (Inc)
(690 V) 80 kA
Rated Current (In)
Main Circuit 250 A
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(500 V) 250 A (690 V) 250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 75 kW (400 V) 140 kW (415 V) 145 kW (500 V) 170 kW (690 V) 250 kW
Rated Operational Voltage
Main Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kiloampere rms
Standards
IEC 60947-3
Switches Operating Mechanism
12 (Between the Poles)
Terminal Type
Lug terminals
Terminal Width
25 mm
Tightening Torque
30 ... 44 N·m
Tightening Torque
30 ... 44 N·m
Object Classification Code
Q
ETIM 8
EC001040 - Fuse switch disconnector
ETIM 9
EC001040 - Fuse switch disconnector
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5291 >> Fuse switch disconnector
eClass
V11.1 : 27371401
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661213
Manufacturer ID
1SCA022746R5530

Specifications may be subject to change without notice