Key Features

  • 1Operate reliably at 1000V in demanding environments.
  • 2Protect against dust and water with front-side IP65 rating.
  • 3Handle heavy-duty applications with 1000A permanent current capacity.
  • 4Mount flexibly using front 4-hole compatible options.
  • 5Ensure safe operation meeting EN60204 and IEC 60947-3 standards.

Need price and lead time?

Request a quote for original ABB OT1000BAUC3TZ. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
1200 mm
Product Net Depth / Length
330 mm
Product Net Weight
69.87 kg
Cable Entry Position
Bottom/Bottom
Cable Outlets Per Side
Blank / 6xC-flange, Knock-outs: 3x10mm, 12.5mm, 2x20.5mm, 2x25.5mm, 2x32.5mm
Connecting Capacity Main Circuit
Hole Diameter 12 mm Screw Clamp / PE Terminal 10pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 1000 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Bottom In - Bottom Out
Position of PE Terminals
Bottom In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 19 W
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V AC) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Recommended Screw Driver
Main Circuit M12
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 75 N·m
Recommended Screw Driver
Main Circuit M12
Tightening Torque
Main Circuit 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642835
E-Number (Sweden)
3140658
Manufacturer ID
1SCA022340R4170

Specifications may be subject to change without notice