OT1000BBAA3A

Product ID:70502
Updated: 2026/4/3
ABB OT1000BBAA3A

Key Features

  • 1Deliver precise energy measurements with ±0.5% accuracy for reliable data. 2、Simplify installation processes to reduce setup time and cost. 3、Meet circularity criteria with verified Environmental Product Declarations. 4、Ensure durability in harsh environments using galvanized steel. 5、Provide comprehensive data analytics to optimize energy consumption patterns.
Product Details
OT1000BBAA3A
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Product Net Width
400 mm
Product Net Height
1200 mm
Product Net Depth / Length
330 mm
Product Net Weight
53 kg
Cable Entry Position
Up/Down
Cable Outlets Per Side
Open / Open
Connecting Capacity Main Circuit
Hole Diameter 12 mm Screw Clamp / PE Terminal 8pcs, 25…120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 1000 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Red / Yellow
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Number of Poles
3P
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V AC) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Standards
IEC 60947-1, -3
ETIM 8
EC000216 - Switch disconnector
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA102812R1001