  • 1Operate a 3-pole front-mounted switch-disconnector with a robust IP65 handle. 2、Simplify installation with a wide phase distance and included terminal bolt kit. 3、Handle high currents rated for 1250 A at 380-415 V, 500 V, and 690 V. 4、Ensure safety compliance by meeting IEC/EN 60664-1 standards with 1000 V insulation. 5、Mount securely on a base with front IP00 protection and reliable lug terminals.
Product Details
OT1250E03W4
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301233D0201
Pollution Degree
3
Product Net Width
454.5 mm
Product Net Height
306 mm
Product Net Depth / Length
145.5 mm
Product Net Weight
16.9 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 1250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 1250 A
Degree of Protection
Front IP00
Distance Between Phases
Phase distance 140 mm
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
6000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 29 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Power AC-23A (Pe)
(400 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Special Functions
Wide phase distance 140
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 03 (Left Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661688
Manufacturer ID
1SCA022866R1760

Specifications may be subject to change without notice