OT125ALUU4BLZ

Product ID:92780
Updated: 2026/4/3
ABB OT125ALUU4BLZ

Key Features

  • 1Handle high currents reliably with a 125A rating. 2、Install flexibly using DIN rail or panel mounting. 3、Meet safety standards with UL98 approval. 4、Save panel space with a compact 103x205x86 mm design. 5、Reduce power loss with robust construction rated at 29W.
Product Details
OT125ALUU4BLZ
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
250 mm
Product Net Height
400 mm
Product Net Depth / Length
180 mm
Product Net Weight
12 kg
Cable Cross-Section
10 ... 70 mm²
Cable Entry Position
Up/Down
Cable Outlets Per Side
Blank / Blank, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm
Conventional Thermal Current (Ithe)
Fully Enclosed 125 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 1 NC
Mounted Auxiliary Contacts
0 NO, 0 NC
Number of Poles
4P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 125 A (690 V) 125 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 105 A (690 V) 50 A
Rated Operational Voltage
Main Circuit 750 V
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA103392R1001

Specifications may be subject to change without notice