- 1Deliver consistent performance for safe and efficient equipment operation. 2、Meet international safety standards including IEC 60947-3 and UL508. 3、Suit motor control centers, switchboards, and industrial control panels. 4、Build with high mechanical endurance for extended lifespan and minimal maintenance. 5、Simplify installation with modular design and adjustable shafts, reducing labor time by up to 50%.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP54 | Product Net Width | 400 mm |
| Product Net Height | 400 mm | Product Net Depth / Length | 230 mm |
| Product Net Weight | 15.3 kg | Cable Entry Position | Down/Down |
| Cable Outlets Per Side | Blank / 2xC-flange, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm | Conventional Thermal Current (Ithe) | Fully Enclosed 160 A |
| Degree of Protection | acc. to IEC 60529 IP54 | Enclosure Material | Steel sheet |
| Handle Color | Black | Handle Type | Pistol handle |
| Maximum Mounted Auxiliary Contacts | 2 NO, 1 NC | Mounted Auxiliary Contacts | 1 NO, 1 NC |
| Number of Poles | 3P | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 V |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 125 A (500 V) 90 A (690 V) 70 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 55 kW (500 V) 55 kW (690 V) 55 kW | Rated Operational Voltage | Main Circuit 750 V |
| Object Classification Code | Q | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 1SCA022609R7340 |