OT125EAUR6TZ
Product ID:91097
Updated: 2026/4/3

Key Features
- 1Ensure robust protection with durable steel sheet enclosures. 2、Prevent personal injury using built-in expander washers and security latches. 3、Apply across diverse industrial needs from 16 to 1250 A. 4、Withstand harsh conditions thanks to an IP65 dust and water ingress rating. 5、Customize solutions with various handle colors and materials.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 400 mm | Product Net Height | 600 mm |
| Product Net Depth / Length | 230 mm | Product Net Weight | 22 kg |
| Cable Cross-Section | 120 mm² | Cable Entry Position | Down/Down |
| Cable Outlets Per Side | Blank / 4xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm | Conventional Thermal Current (Ithe) | Fully Enclosed 160 A |
| Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Steel sheet |
| Handle Color | Black | Handle Type | Pistol handle |
| Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC | Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Number of Poles | 6P | Pollution Degree | 3 |
| Position of Line Terminals | Bottom In - Bottom Out | Position of PE Terminals | Bottom In - Bottom Out |
| Power Loss | at Rated Operating Conditions per Pole 4 W | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 V |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 125 A (500 V) 90 A (690 V) 70 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 55 kW (500 V) 55 kW (690 V) 55 kW | Rated Operational Voltage | Main Circuit 750 V |
| Object Classification Code | Q | WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| E-Number (Finland) | 3642840 | Manufacturer ID | 1SCA022325R0350 |
Specifications may be subject to change without notice