OT125GFCC6T
Product ID:85999
Updated: 2026/4/4

Key Features
- 1Deliver high-performance protection for 6-pole, 400V AC23, 125A applications. 2、Ensure reliable operation with a robust plastic enclosure rated IP65. 3、Operate effortlessly using the integrated black pistol handle. 4、Enhance safety with an interlocked cover for secure access. 5、Install versatility for front mounting and distribution boards.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 380 mm | Product Net Height | 560 mm |
| Product Net Depth / Length | 180 mm | Product Net Weight | 8 kg |
| Cable Cross-Section | 10 ... 70 mm² | Cable Entry Position | Top/Bottom |
| Cable Outlets Per Side | II-flange / II-flange | Connecting Capacity Main Circuit | Screw Clamp 10 ... 70 mm² Screw Clamp / PE Terminal 2pc,10 ... 70 mm² |
| Conventional Thermal Current (Ithe) | Fully Enclosed 125 A | Degree of Protection | acc. to IEC 60529 IP65 |
| Enclosure Material | Plastic | Enclosure Type | Fibox |
| Handle Color | Black | Handle Type | Pistol handle |
| Impact Resistance Rating | Housing IK08 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Mounted Auxiliary Contacts | 2 NO, 2 NC | Neutral Type | No neutral terminal |
| Number of Auxiliary Contacts NC | 2 | Number of Auxiliary Contacts NO | 2 |
| Number of Poles | 6P | Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out | Rated Conditional Short-Circuit Current (Inc) | 24 kA |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 55 kW (500 V) 75 kW (690 V) 110 kW | Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 12 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 4 kA |
| Recommended Screw Driver | Main Circuit Hexagon 4 | Standards | IEC 60947-1, -3 |
| Terminal Type | Screw Terminals | Tightening Torque | Main Circuit 6 N·m |
| Wire Stripping Length | 20 mm | Wire Stripping Length | 20 mm |
| Recommended Screw Driver | Main Circuit Hexagon 4 | Tightening Torque | Main Circuit 6 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
| IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) | E-Number (Sweden) | 3134577 |
| Manufacturer ID | 1SCA148668R1001 |
Specifications may be subject to change without notice