OT125GLRR6TZ
Product ID:87124
Updated: 2026/4/4

Key Features
- 1Ensure UV protection and resistance to low-pressure water ingress. 2、Select for outdoor use with enhanced UV light resistance. 3、Prevent accidental operation to ensure personnel safety. 4、Secure the handle for added safety and tamper resistance. 5、Support up to 125A at 400V AC23 for reliable performance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 400 mm | Product Net Height | 400 mm |
| Product Net Depth / Length | 230 mm | Product Net Weight | 16.4 kg |
| Cable Cross-Section | 10 ... 70 mm² | Cable Entry Position | Top/Bottom |
| Cable Outlets Per Side | 4xring-flange / 4xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm | Connecting Capacity Main Circuit | Screw Clamp 10 ... 70 mm² Screw Clamp / PE Terminal 4pc,10 ... 70 mm² |
| Conventional Thermal Current (Ithe) | Fully Enclosed 125 A | Degree of Protection | acc. to IEC 60529 IP65 |
| Enclosure Material | Steel sheet | Enclosure Type | MSC |
| Handle Color | Black | Handle Type | Pistol handle |
| Impact Resistance Rating | Housing IK09 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Mounted Auxiliary Contacts | 2 NO, 2 NC | Neutral Type | No neutral terminal |
| Number of Auxiliary Contacts NC | 2 | Number of Auxiliary Contacts NO | 2 |
| Number of Poles | 6P | Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out | Rated Conditional Short-Circuit Current (Inc) | 24 kA |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 55 kW (500 V) 75 kW (690 V) 110 kW | Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 12 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 4 kA |
| Recommended Screw Driver | Main Circuit Hexagon 4 | Standards | IEC 60947-1, -3 |
| Terminal Type | Screw Terminals | Tightening Torque | Main Circuit 6 N·m |
| Wire Stripping Length | 20 mm | Wire Stripping Length | 20 mm |
| Recommended Screw Driver | Main Circuit Hexagon 4 | Tightening Torque | Main Circuit 6 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
| IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | E-Number (Sweden) | 3134584 |
| Manufacturer ID | 1SCA148479R1001 |
Specifications may be subject to change without notice