- 1Deliver high performance for demanding applications with reliable operation. 2、Save space using a compact, modular design for easier installation. 3、Enhance safety with visible contacts and door interlock features. 4、Install flexibly in any position with multiple mounting options. 5、Meet global standards including UL98 and IEC 60947-3.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 250 mm | Product Net Height | 400 mm |
| Product Net Depth / Length | 180 mm | Product Net Weight | 9.5 kg |
| Cable Cross-Section | 10 ... 70 mm² | Cable Entry Position | Top/Bottom |
| Cable Outlets Per Side | Blank /Blank, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm, 40.5mm | Connecting Capacity Main Circuit | Screw Clamp 10 ... 70 mm² Screw Clamp / PE Terminal 2pc,10 ... 70 mm² |
| Conventional Thermal Current (Ithe) | Fully Enclosed 125 A | Degree of Protection | acc. to IEC 60529 IP65 |
| Enclosure Material | Steel sheet | Enclosure Type | MSC |
| Handle Color | Black | Handle Type | Pistol handle |
| Impact Resistance Rating | Housing IK09 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Mounted Auxiliary Contacts | 0 NO, 0 NC | Neutral Type | Switchable neutral |
| Number of Auxiliary Contacts NC | 0 | Number of Auxiliary Contacts NO | 0 |
| Number of Poles | 4P | Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out | Rated Conditional Short-Circuit Current (Inc) | 24 kA |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 125 A (690 V) 125 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 55 kW (500 V) 75 kW (690 V) 110 kW | Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 12 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 4 kA |
| Standards | IEC 60947-1, -3 | Terminal Type | Screw Terminals |
| Tightening Torque | Main Circuit 6 N·m | Wire Stripping Length | 20 mm |
| Wire Stripping Length | 20 mm | Tightening Torque | Main Circuit 6 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
| IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | Manufacturer ID | 1SCA148276R1001 |
Specifications may be subject to change without notice