ABB OT160ELCC6AZ

Key Features

  • 1Ensure reliable operation with a high thermal current rating. 2、Protect against harsh conditions with an IP65-rated robust enclosure. 3、Meet EU RoHS safety standards for compliance. 4、Simplify installation in demanding industrial environments. 5、Apply versatile design across various applications.
Product Details
OT160ELCC6AZ
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
600 mm
Product Net Depth / Length
230 mm
Product Net Weight
29 kg
Cable Cross-Section
120 mm²
Cable Entry Position
Up/Down
Cable Outlets Per Side
2xC-flange / 2xC-flange, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Red / Yellow
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 2 NC
Number of Poles
6P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 135 A (500 V) 125 A (690 V) 80 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 75 kW (500 V) 75 kW (690 V) 75 kW
Rated Operational Voltage
Main Circuit 750 V
Object Classification Code
Q
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022512R8110