OT160EVFCC4B

Product ID:83186
Updated: 2026/4/4
ABB OT160EVFCC4B

Key Features

  • 1Handle high current loads up to 160A and 88 kW. 2、Protect against harsh conditions with an IP65-rated, UV-resistant enclosure. 3、Secure operations using the padlockable handle for up to three padlocks. 4、Ensure operator safety with a defeatable interlocked cover system. 5、Simplify installation via versatile top and bottom cable entries.
Product Details
OT160EVFCC4B
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
280 mm
Product Net Height
380 mm
Product Net Depth / Length
130 mm
Product Net Weight
4.3 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
II-flange / II-flange
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 2pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Enclosure Type
Fibox
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
0 NO, 0 NC
Neutral Type
Switchable neutral
Number of Auxiliary Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Poles
4P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 88 kW (500 V) 112 kW (690 V) 144 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Standards
IEC 60947-1, -3
Terminal Type
Bolt
Tightening Torque
Main Circuit 6 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA148617R1001

Specifications may be subject to change without notice