OT16ETMM3TE
Product ID:84235
Updated: 2026/4/4

Key Features
- 1Construct durable alu-zinc coated steel with polyester powder coating. 2、Deploy outdoors with UV, water, and immersion resistance per UL746C. 3、Ensure safety with an interlocked cover that prevents opening when powered. 4、Meet EMC standards for reliable operation in diverse electrical environments. 5、Install easily in distribution boards using various cable entries and glands.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 150 mm | Product Net Height | 200 mm |
| Product Net Depth / Length | 100 mm | Product Net Weight | 1.7 kg |
| Cable Cross-Section | 0.75 ... 10 mm² | Cable Entry Position | Top and/or Bottom |
| Cable Outlets Per Side | 2xø25.5+ø16.5 / 2xø25.5+ø16.5 | Connecting Capacity Main Circuit | Screw Clamp 0.75 ... 10 mm² Screw Clamp / PE Terminal 2pc,1.5 ... 25 mm² |
| Conventional Thermal Current (Ithe) | Fully Enclosed 40 A | Degree of Protection | acc. to IEC 60529 IP65 |
| Enclosure Material | Steel sheet | Handle Color | Black |
| Handle Type | Selector handle | Impact Resistance Rating | Housing IK09 |
| Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC | Mounted Auxiliary Contacts | 1 NO, 0 NC |
| Neutral Type | No neutral terminal | Number of Auxiliary Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 | Number of Poles | 3P |
| Pollution Degree | 3 | Power Loss | at Rated Operating Conditions per Pole 1.6 W |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 V | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 32 A (500 V) 32 A (690 V) 32 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 16 A (500 V) 16 A (690 V) 10 A | Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 7.5 kW (500 V) 7.5 kW (690 V) 7.5 kW |
| Rated Operational Voltage | Main Circuit 750 V | Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 0.705 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 0.5 kA | Recommended Screw Driver | Main Circuit Pozidriv 2 |
| Special Functions | EMC | Standards | IEC 60947-1, -3 |
| Tightening Torque | Main Circuit 0.8 N·m | Wire Stripping Length | 10 mm |
| Wire Stripping Length | 10 mm | Recommended Screw Driver | Main Circuit Pozidriv 2 |
| Tightening Torque | Main Circuit 0.8 N·m | Object Classification Code | Q |
| ETIM 8 | EC000216 - Switch disconnector | ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| UNSPSC | 39122205 | IDEA Granular Category Code (IGCC) | 5166 >> Safety switch |
| eClass | V11.1 : 27371403 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| E-Number (Finland) | 3601738 | E-Number (Norway) | 1429470 |
| E-Number (Sweden) | 3141204 | Manufacturer ID | 1SCA022734R5980 |
Specifications may be subject to change without notice