OT16FT4N2

Product ID:87037
Updated: 2026/4/4
ABB OT16FT4N2

Key Features

  • 1Optimize panel space with a compact design for control panels and MCCs. 2、Ensure secure connections using front-operated screw clamp terminals. 3、Simplify installation with versatile door mounting options. 4、Protect against solid objects with an IP20 enclosure type. 5、Meet global safety standards including IEC, UL, and CSA compliance.
Product Details
OT16FT4N2
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301262D0201
Pollution Degree
3
Product Net Width
48.5 mm
Product Net Height
54 mm
Product Net Depth / Length
52 mm
Product Net Weight
0.13 kg
Cable Cross-Section
Cu 0.75 ... 10 mm²
Connecting Capacity Main Circuit
Flexible with Ferrule 1x Cu 0.75…4 mm² Solid 1x Cu 0.75…6 mm² Flexible 1x Cu 0.75…10 mm² Stranded 1x Cu 0.75…10 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 25 A
Conventional Thermal Current (Ithe)
Fully Enclosed 25 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Door mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 0.3 W
Rated Conditional Short-Circuit Current (Inc)
(40 A fuse, ≤415V) 50 kA (25 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 16 A (500 V) 16 A (690 V) 16 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 16 A (500 V) 16 A (690 V) 16 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 16 A (500 V) 16 A (690 V) 10 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 3 kW (400 ... 415 V) 7.5 kW (500 V) 7.5 kW (690 V) 7.5 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 0.71 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 0.5 kA
Recommended Screw Driver
Main Circuit Pozidriv 2
Special Functions
No
Standards
IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Switches Operating Mechanism
Mechanism on Top of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 0.8 N·m
Wire Stripping Length
Main Circuit 9-10 mm
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
20 A
Horsepower Rating UL/CSA
(110 ... 120 V AC) Single Phase 1 Hp (240 V AC) Single Phase 2 Hp (440 ... 480 V AC) Single Phase 5 Hp (550 ... 600 V AC) Single Phase 7.5 Hp (220 ... 240 V AC) Three Phase 5 Hp (440 ... 480 V AC) Three Phase 10 Hp (550 ... 600 V AC) Three Phase 10 Hp
Wire Stripping Length
Main Circuit 9-10 mm
Recommended Screw Driver
Main Circuit Pozidriv 2
Tightening Torque
acc. IEC 60947-1 0.8 N·m
Tightening Torque UL/CSA
7 in·lb
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601427
E-Number (Norway)
4363535
E-Number (Sweden)
3171082
Manufacturer ID
1SCA105711R1001

Specifications may be subject to change without notice