OT250ENUR3TZ

Product ID:93462
Updated: 2026/4/3
ABB OT250ENUR3TZ

Key Features

  • 1Deliver high-performance switching for currents from 16 to 2000 amperes. 2、Ensure reliable operation with a robust non-fused disconnect design. 3、Install flexibly using DIN Rail or standard panel mounting options. 4、Meet IEC 60947-3 standards for guaranteed safety and compliance. 5、Save costs with available bulk pricing for large-scale projects.
Product Details
OT250ENUR3TZ
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Product Net Width
400 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
33 kg
Cable Entry Position
Down/Down
Cable Outlets Per Side
Blank / 4xRing-flange+ø25.5
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 4pcs, 25…120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Stainless Steel
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Number of Poles
3P
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 132 kW (500 V) 160 kW (690 V) 200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
EMC
Standards
IEC 60947-1, -3
ETIM 8
EC000216 - Switch disconnector
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA132247R1001

Specifications may be subject to change without notice