Key Features

  • 1Ensure safe operation with a secure, tamper-proof design.
  • 2Handle up to 200KW with a reliable 3-pole configuration.
  • 3Protect against dust and water with an IP65 enclosure rating.
  • 4Enhance UV resistance and durability for outdoor applications.
  • 5Resist corrosion with a galvanized steel and polyester coating.

Need price and lead time?

Request a quote for original ABB OT400DAUA3TZ. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
26.55 kg
Cable Entry Position
Down/Down
Cable Outlets Per Side
Blank / Open
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 4pcs, 25…120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Number of Poles
3P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Standards
IEC 60947-1, -3
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA022299R1740

Specifications may be subject to change without notice

Still deciding on OT400DAUA3TZ?

Our engineers can confirm stock, price, and lead time for this ABB part.

Get a no-obligation quote in 1 minute.

Chat with us