ABB OT400DDCC3A

Key Features

  • 1Utilize a rigid glass reinforced polycarbonate enclosure for durability. 2、Handle high operational currents and voltages reliably. 3、Benefit from UV protection for outdoor longevity. 4、Achieve IP65 protection against dust and water. 5、Customize configurations to meet specific needs.
Product Details
OT400DDCC3A
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
380 mm
Product Net Height
840 mm
Product Net Depth / Length
180 mm
Product Net Weight
16 kg
Cable Entry Position
Up/Down
Cable Outlets Per Side
II-flange / II-flange
Connecting Capacity Main Circuit
Hole Diameter 10 mm Screw Clamp / PE Terminal 4pcs, 25…120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 400 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Handle Color
Red / Yellow
Handle Type
Pistol handle
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Number of Poles
3P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 10 W
Rated Conditional Short-Circuit Current (Inc)
61.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 220 kW (500 V) 280 kW (690 V) 355 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 65 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 15 kA
Standards
IEC 60947-1, -3
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA110552R1001

Specifications may be subject to change without notice