OT400DDUU3BZ
Product ID:93317
Updated: 2026/4/3

Key Features
- 1Reduce touch risk with a finger-proof safety design. 2、Simplify installation and upkeep via modular construction. 3、Ensure reliable operation with superior short-circuit protection. 4、Add security by padlocking handles in the OFF position. 5、Achieve fast switching via quick make/break mechanism.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
| Product Net Width | 400 mm | Product Net Height | 800 mm |
| Product Net Depth / Length | 230 mm | Product Net Weight | 30 kg |
| Cable Entry Position | Up/Up | Cable Outlets Per Side | Blank / Blank |
| Connecting Capacity Main Circuit | Hole Diameter 10 mm Screw Clamp / PE Terminal 4pcs, 25â¦120 mm² | Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
| Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Steel sheet |
| Handle Color | Black | Handle Type | Pistol handle |
| Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC | Mounted Auxiliary Contacts | 0 NO, 0 NC |
| Number of Poles | 3P | Pollution Degree | 3 |
| Power Loss | at Rated Operating Conditions per Pole 10 W | Rated Conditional Short-Circuit Current (Inc) | 61.5 kA |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A (690 V) 400 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A (690 V) 400 A | Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (1000 V AC) 65 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 15 kA |
| Standards | IEC 60947-1, -3 | Object Classification Code | Q |
| ETIM 8 | EC000216 - Switch disconnector | WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) |
| Manufacturer ID | 1SCA124693R1001 |
Specifications may be subject to change without notice