OT630KLCC4TZ

Product ID:83756
Updated: 2026/4/4
ABB OT630KLCC4TZ

Key Features

  • 1Handle up to 570A for reliable operation in demanding environments. 2、Ensure robust IP65 protection against dust and water ingress. 3、Provide durable performance with a steel enclosure for harsh conditions. 4、Deliver reliable switching and isolation for safe electrical operation. 5、Back your purchase with a comprehensive 3-year warranty.
Product Details
OT630KLCC4TZ
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
1000 mm
Product Net Depth / Length
230 mm
Product Net Weight
31.45 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
2xC-flange / 2xC-flange, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 12 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 570 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
Switchable neutral
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
4P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Position of PE Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 25 W
Rated Conditional Short-Circuit Current (Inc)
90 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 570 A (500 V) 570 A (690 V) 570 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 570 A (500 V) 570 A (690 V) 570 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 315 kW (500 V) 400 kW (690 V) 560 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 80 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 20 kA
Recommended Screw Driver
Main Circuit M12
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 75 N·m
Recommended Screw Driver
Main Circuit M12
Tightening Torque
Main Circuit 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Sweden)
3135046
Manufacturer ID
1SCA022461R6130

Specifications may be subject to change without notice