OT63FT4N2
Product ID:86255
Updated: 2026/4/4

Key Features
- 1Deploy a 4-pole, front-operated switch-disconnector with protected clamp terminals. 2、Ensure high reliability and meet IEC, UL, and CSA safety standards. 3、Handle rated operational currents of 63 A at 380-415 V, 500 V, and 690 V. 4、Rely on a 63 A conventional thermal current at 40 °C fully enclosed. 5、Accelerate installation with a modular design for flexible low-voltage systems.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | Front IP20 | Environmental Information | 1SCC301263D0201 |
| Pollution Degree | 3 | Product Net Width | 70 mm |
| Product Net Height | 72 mm | Product Net Depth / Length | 69 mm |
| Product Net Weight | 0.32 kg | Cable Cross-Section | Cu 1.5 ... 35 mm² |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1x Cu 1.5â¦4 mm² Solid 1x Cu 1.5â¦6 mm² Flexible 1x Cu 1.5â¦35 mm² Stranded 1x Cu 1.5â¦35 mm² | Conventional Free-air Thermal Current (Ith) | Î = 40 °C 63 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 63 A | Degree of Protection | Front IP20 |
| Distance Between Phases | Standard | Fourth Pole Position | Right Side |
| Fourth Pole Type | Switched - Simultaneous Function | Handle Type | Handle and shaft not included |
| Lock Type | No | Mechanical Durability | 20000 |
| Mounting Type | Door mounting | Number of Poles | 4P |
| Operating Mode | Front operated | Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out Bottom In - Top Out | Power Loss | at Rated Operating Conditions per Pole 2.8 W |
| Rated Conditional Short-Circuit Current (Inc) | (100 A fuse, â¤415 V) 50 kA (100 A fuse, 500 V) 100 kA (80 A fuse, 690 V) 50 kA | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 V | Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 63 A (500 V) 63 A (690 V) 63 A |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 63 A (500 V) 63 A (690 V) 63 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 63 A (500 V) 45 A (690 V) 20 A |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 11 kW (400 ... 415 V) 22 kW (500 V) 22 kW (690 V) 15 kW | Rated Operational Voltage | Main Circuit 750 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V) 2.1 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 1.5 kA |
| Recommended Screw Driver | Main Circuit Pozidriv 2 | Special Functions | No |
| Standards | IEC 60947-3 / UL 508 / CSA C22.2 No. 14 | Switches Operating Mechanism | Mechanism on Top of the Switch |
| Terminal Type | Screw Terminals | Tightening Torque | acc. IEC 60947-1 2 N·m |
| Wire Stripping Length | Main Circuit 10-12 mm | Maximum Operating Voltage UL/CSA | 600 V |
| Ampere Rating | 60 A | Horsepower Rating UL/CSA | (110 ... 120 V AC) Single Phase 2 Hp (240 V AC) Single Phase 7.5 Hp (440 ... 480 V AC) Single Phase 15 Hp (550 ... 600 V AC) Single Phase 15 Hp (220 ... 240 V AC) Three Phase 15 Hp (440 ... 480 V AC) Three Phase 30 Hp (550 ... 600 V AC) Three Phase 30 Hp |
| Wire Stripping Length | Main Circuit 10-12 mm | Recommended Screw Driver | Main Circuit Pozidriv 2 |
| Tightening Torque | acc. IEC 60947-1 2 N·m | Tightening Torque UL/CSA | 18 in·lb |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122233 |
| IDEA Granular Category Code (IGCC) | 5290 >> Disconnect switch | eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | E-Number (Finland) | 3601456 |
| E-Number (Norway) | 4363541 | E-Number (Sweden) | 3171085 |
| Manufacturer ID | 1SCA105393R1001 |
Specifications may be subject to change without notice