OT80G2-3DS

Product ID:89762
Updated: 2026/4/3
ABB OT80G2-3DS

Key Features

  • 1Deliver high performance and reliability in extreme operating conditions. 2、Utilize a compact design to save valuable panel space. 3、Integrate advanced safety features for enhanced personnel and equipment protection. 4、Apply in industrial applications that demand uncompromising reliability. 5、Comply with IEC 60947 technical standards for assured electrical safety.
Product Details
OT80G2-3DS
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301333D0201
Pollution Degree
3
Product Net Width
64 mm
Product Net Height
81 mm
Product Net Depth / Length
70 mm
Product Net Weight
0.267 kg
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x Cu 1.5…4 mm² Solid 1/2x Cu 1.5…6 mm² Flexible 1x Cu 1.5…35 mm² Flexible 2x Cu 1.5…16 mm² Stranded 1x Cu 1.5…35 mm² Stranded 2x Cu 1.5…16 mm²
Conventional Free-air Thermal Current (Ith)
80 A
Conventional Thermal Current (Ithe)
80 A
Degree of Protection
Front IP20
Handle Type
Handle not included
Maximum Mounted Auxiliary Contacts
4 NO, 4 NC
Mechanical Durability
Nr. Operations 100000
Mounting Type
Door mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 3.4 W
Rated Conditional Short-Circuit Current (Inc)
(80 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC 60947-1 800 V
Rated Operational Current AC-21A (Ie)
(415 V) 80 A (690 V) 80 A
Rated Operational Current AC-22A (Ie)
(415 V) 80 A (690 V) 80 A
Rated Operational Current AC-23A (Ie)
(415 V) 80 A (690 V) 40 A
Rated Operational Power AC-23A (Pe)
(415 V) 45 kW (690 V) 37 kW
Rated Operational Voltage
Main Circuit 800 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 3.5 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 1.5 kA for 0.2 s 2.5 kA
Recommended Screw Driver
Main Circuit Pozidriv 2
Special Functions
No
Standards
IEC60947-3 UL60947-4-1 CSA C22.2 No.14
Switches Operating Mechanism
Mechanism on Top of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 2 N·m
Wire Stripping Length
Main Circuit 13-16 mm Main Circuit 0.51-0.63 in
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
80 A
Horsepower Rating UL/CSA
(110 ... 120 V AC) Single Phase 2 Hp (240 V AC) Single Phase 10 Hp (440 ... 480 V AC) Single Phase 20 Hp (550 ... 600 V AC) Single Phase 20 Hp (110 ... 120 V AC) Three Phase 5 Hp (240 V AC) Three Phase 20 Hp (440 ... 480 V AC) Three Phase 40 Hp (550 ... 600 V AC) Three Phase 40 Hp
Wire Size
1x 16-2 AWG 2x 16-8 AWG
Wire Stripping Length
Main Circuit 13-16 mm Main Circuit 0.51-0.63 in
Recommended Screw Driver
Main Circuit Pozidriv 2
Tightening Torque
acc. IEC 60947-1 2 N·m
Tightening Torque UL/CSA
UL 18 lbf·in
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA162569R1001

Specifications may be subject to change without notice