OTM125F4M230V

Product ID:85842
Updated: 2026/7/15
ABB OTM125F4M230V

Key Features

  • 1Handle high-current loads up to 125 Amps for robust performance.
  • 2Utilize a four-pole configuration for enhanced safety and reliability.
  • 3Control operations easily with motorized drive and direct mount handle.
  • 4Ensure secure electrical isolation with a rated insulation voltage of 800V.
  • 5Rely on a durable design with a reference lifetime of 20 years.

Need price and lead time?

Request a quote for original ABB OTM125F4M230V. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP20
Pollution Degree
3
Product Net Width
186.5 mm
Product Net Height
100 mm
Product Net Depth / Length
116 mm
Product Net Weight
1 kg
Cable Cross-Section
Cu 10 ... 70 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 125 A
Conventional Thermal Current (Ithe)
Fully Enclosed 125 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
20000
Motor Operational Voltage
110 ... 240 V AC/DC
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 6.3 W
Rated Conditional Short-Circuit Current (Inc)
(125 A fuse, 415 V) 50 kA (125 A fuse, 690 V) 18 kA (63 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 90 A (500 V) 70 A (690 V) 50 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 22 kW (400 ... 415 V) 45 kW (500 V) 45 kW (690 V) 45 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 3.6 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 2.5 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 6 N·m
Tightening Torque
acc. IEC 60947-1 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA122973R1001

Specifications may be subject to change without notice

Still deciding on OTM125F4M230V?

Our engineers can confirm stock, price, and lead time for this ABB part.

Get a no-obligation quote in 1 minute.

Chat with us