OTM1600E4CM24D
Product ID:85929
Updated: 2026/4/4

Key Features
- 1Handle high currents up to 1600A for efficient power distribution. 2、Enable precise motorized operation with a long turning handle. 3、Withstand short-circuit currents up to 50kA with robust construction. 4、Mount flexibly in distribution boards or on surfaces. 5、Operate manually with the included handle, clips, and hardware kit.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | Front IP20 | Environmental Information | 1SCC303036D0202 |
| Pollution Degree | 3 | Product Net Width | 587 mm 23.11 in |
| Product Net Height | 372 mm 14.65 in | Product Net Depth / Length | 372 mm 14.65 in |
| Product Net Weight | 69 kg 152.12 lb | Conventional Free-air Thermal Current (Ith) | Π= 40 °C 1600 A |
| Degree of Protection | Front IP20 | Distance Between Phases | Standard |
| Fourth Pole Position | Right Side | Fourth Pole Type | Switched - Simultaneous Function |
| Handle Color | Black | Handle Type | Direct mounted handle |
| Motor Operational Voltage | 24 V DC | Mounting Type | Base mounting |
| Number of Poles | 4P | Operating Mode | Front operated |
| Pollution Degree | 3 | Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
| Power Loss | at Rated Operating Conditions per Pole 48 W | Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 1600 A (500 V) 1600 A (690 V) 1600 A |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 1600 A (500 V) 1600 A (690 V) 1600 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 1600 A (500 V) 1600 A (690 V) 1600 A |
| Rated Operational Current AC-31B (Ie) | (380 ... 415 V) 1600 A | Rated Operational Current AC-33B (Ie) | (380 ... 415 V) 1000 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW | Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kiloampere rms | Switches Operating Mechanism | Mechanism at the End of the Switch |
| Terminal Type | Screw Terminals | Tightening Torque | acc. IEC 60947-1 50 ... 75 N·m |
| Transition Type | Open | Tightening Torque | acc. IEC 60947-1 50 ... 75 N·m |
| Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) | eClass | V11.1 : 27371403 |
| WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) | E-Number (Finland) | 3641795 |
| Manufacturer ID | 1SCA113676R1001 |
Specifications may be subject to change without notice