OTM160E3CM48D

Product ID:87354
Updated: 2026/4/4
ABB OTM160E3CM48D

Key Features

  • 1Handle high currents up to 160A for efficient power distribution. 2、Operate easily with a motorized mechanism and black handle. 3、Ensure reliable performance with a robust pollution degree 3 design. 4、Save installation space with compact H150mm x W273mm x D197mm dimensions. 5、Secure connections using drilled flat pads and M8 bolt kit.
Product Details
OTM160E3CM48D
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC303036D0202
Pollution Degree
3
Product Net Width
273 mm 10.75 in
Product Net Height
150 mm 5.91 in
Product Net Depth / Length
197 mm 7.76 in
Product Net Weight
5.6 kg 12.35 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 160 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Direct mounted handle
Motor Operational Voltage
48 V DC
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 2.4 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 160 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 160 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 90 kW (500 V) 110 kW (690 V) 160 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kiloampere rms
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Transition Type
Open
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3641697
Manufacturer ID
1SCA022845R8450