OTM160E3WM230C
Product ID:85554
Updated: 2026/4/4

Key Features
- 1Deliver high performance with a rated insulation voltage of 1000 V. 2、Operate manually using the included handle for emergencies. 3、Simplify installation with the provided terminal bolt kit. 4、Organize accessories using the storage clip for the handle and spare fuses. 5、Save panel space with a compact design measuring 296x150x198 mm.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | Front IP00 | Pollution Degree | 3 |
| Product Net Width | 296 mm | Product Net Height | 150 mm |
| Product Net Depth / Length | 198 mm | Product Net Weight | 5.2 kg |
| Conventional Free-air Thermal Current (Ith) | Π= 40 °C 200 A | Conventional Thermal Current (Ithe) | Fully Enclosed 160 A |
| Degree of Protection | Front IP00 | Distance Between Phases | Wide phase distance |
| Handle Color | Black | Handle Type | Direct mounted handle |
| Lock Type | Yes | Mechanical Durability | 20000 |
| Motor Operational Voltage | 220 ... 240 V AC | Mounting Type | Base mounting |
| Number of Poles | 3P | Operating Mode | Front operated |
| Pollution Degree | 3 | Position of Line Terminals | Top In - Bottom Out |
| Power Loss | at Rated Operating Conditions per Pole 3.2 W | Rated Conditional Short-Circuit Current (Inc) | (315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 200 A (500 V) 200 A (690 V) 160 A (1000 V AC) 160 A | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 200 A (500 V) 200 A (690 V) 160 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A | Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 48 kW (400 ... 415 V) 80 kW (500 V) 112 kW (690 V) 144 kW |
| Rated Operational Voltage | Main Circuit 1000 V | Rated Short-Circuit Making Capacity (Icm) | (690 V) 30 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 8 kA | Special Functions | Wide phase distance |
| Standards | IEC 60947-3 | Switches Operating Mechanism | Mechanism at the End of the Switch |
| Terminal Type | Screw Terminals | Tightening Torque | acc. IEC 60947-1 15 ⦠22 N·m |
| Tightening Torque | acc. IEC 60947-1 15 ⦠22 N·m | Object Classification Code | Q |
| ETIM 8 | EC000216 - Switch disconnector | ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| eClass | V11.1 : 27371403 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 1SCA115286R1001 |