Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP20
Pollution Degree
3
Product Net Width
238 mm 9.37 in
Product Net Height
150 mm 5.91 in
Product Net Depth / Length
197 mm 7.76 in
Product Net Weight
3.7 kg 8.16 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 200 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Direct mounted handle
Motor Operational Voltage
220 ... 240 V AC
Mounting Type
Base mounting
Number of Poles
2P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 200 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 200 A
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kiloampere rms
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Transition Type
Open
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403