OTM200E3M230C
Product ID:85434
Updated: 2026/4/4

Key Features
- 1Utilize a high-performance motorized switch-disconnector with robust construction. 2、Install easily in confined spaces thanks to its compact design. 3、Customize with various handles, shafts, and auxiliary contacts. 4、Apply across diverse machinery, power distribution, and PV installations. 5、Meet high safety standards with 1000 V insulation and 12 kV impulse withstand.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Degree of Protection | Front IP00 | Pollution Degree | 3 |
| Product Net Width | 296 mm | Product Net Height | 150 mm |
| Product Net Depth / Length | 181 mm | Product Net Weight | 5.1 kg |
| Conventional Free-air Thermal Current (Ith) | Π= 40 °C 200 A | Conventional Thermal Current (Ithe) | Fully Enclosed 200 A |
| Degree of Protection | Front IP00 | Distance Between Phases | Standard |
| Handle Color | Black | Handle Type | Direct mounted handle |
| Lock Type | Yes | Mechanical Durability | 20000 |
| Motor Operational Voltage | 220 ... 240 V AC | Mounting Type | Base mounting |
| Number of Poles | 3P | Operating Mode | Front operated |
| Pollution Degree | 3 | Position of Line Terminals | Top In - Bottom Out |
| Power Loss | at Rated Operating Conditions per Pole 4.0 W | Rated Conditional Short-Circuit Current (Inc) | (315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 200 A (500 V) 200 A (690 V) 160 A (1000 V AC) 160 A | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 200 A (500 V) 200 A (690 V) 200 A | Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 60 kW (400 ... 415 V) 110 kW (500 V) 132 kW (690 V) 200 kW |
| Rated Operational Voltage | Main Circuit 1000 V | Rated Short-Circuit Making Capacity (Icm) | (690 V) 30 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 8 kA | Special Functions | No |
| Standards | IEC 60947-3 | Switches Operating Mechanism | Mechanism at the End of the Switch |
| Terminal Type | Lug terminals | Tightening Torque | acc. IEC 60947-1 15 ⦠22 N·m |
| Tightening Torque | acc. IEC 60947-1 15 ⦠22 N·m | Object Classification Code | Q |
| ETIM 8 | EC000216 - Switch disconnector | ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| eClass | V11.1 : 27371403 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 1SCA115284R1001 |
Specifications may be subject to change without notice