OTM40F4CMA230V

Product ID:84398
Updated: 2026/7/15
ABB OTM40F4CMA230V

Key Features

  • 1Handle up to 40A across multiple voltage ranges (380-415V, 500V, 690V).
  • 2Enhance safety with a fully enclosed, durable construction.
  • 3Control easily via a front-operated, direct-mounted handle.
  • 4Incorporate IO-II function and withstand 8 kV rated impulse.
  • 5Meet CE and RoHS standards for full compliance.

Need price and lead time?

Request a quote for original ABB OTM40F4CMA230V. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP20
Pollution Degree
3
Product Net Width
283 mm 11.14 in
Product Net Height
100 mm 3.94 in
Product Net Depth / Length
116 mm 4.57 in
Product Net Weight
1.86 kg 4.1 lb
Cable Cross-Section
2.5 ... 16 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 40 A
Conventional Thermal Current (Ithe)
Fully Enclosed 40 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Direct mounted handle
Motor Operational Voltage
110 ... 240 V AC/DC
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 1.6 W
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 40 A (500 V) 40 A (690 V) 40 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 40 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 40 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 18.5 kW (500 V) 22 kW (690 V) 37 kW
Rated Operational Voltage
Main Circuit 800 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 2.5 kiloampere rms
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 6 N·m
Transition Type
Open
Tightening Torque
acc. IEC 60947-1 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601227
Manufacturer ID
1SCA120102R1001

Specifications may be subject to change without notice

Still deciding on OTM40F4CMA230V?

Our engineers can confirm stock, price, and lead time for this ABB part.

Get a no-obligation quote in 1 minute.

Chat with us