OTM80F3M230V

Product ID:85863
Updated: 2026/4/4
ABB OTM80F3M230V

Key Features

  • 1Achieve high insulation voltage up to 800 V for reliable operation. 2、Ensure robust mechanical endurance with 20,000 operation cycles. 3、Utilize an adjustable shaft for external handles for flexible installation. 4、Benefit from a compact design with dimensions: 100 mm x 230 mm x 116 mm. 5、Simplify installation with an included bolt kit for all terminals.
Product Details
OTM80F3M230V
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Degree of Protection
Front IP20
Pollution Degree
3
Product Net Width
160 mm
Product Net Height
100 mm
Product Net Depth / Length
116 mm
Product Net Weight
0.9 kg
Cable Cross-Section
Cu 1.5 ... 35 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 80 A
Conventional Thermal Current (Ithe)
Fully Enclosed 80 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Direct mounted handle
Lock Type
Yes
Mechanical Durability
20000
Motor Operational Voltage
110 ... 240 V AC/DC
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 4.5 W
Rated Conditional Short-Circuit Current (Inc)
(125 A fuse, 415 V) 50 kA (125 A fuse, 690 V) 18 kA (63 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 80 A (500 V) 80 A (690 V) 80 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 80 A (500 V) 80 A (690 V) 80 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 75 A (500 V) 58 A (690 V) 20 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 22 kW (400 ... 415 V) 37 kW (500 V) 37 kW (690 V) 18.5 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 2.1 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 1.5 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 2 N·m
Tightening Torque
acc. IEC 60947-1 2 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA122970R1001

Specifications may be subject to change without notice