T1N160 TMD125-1250 4pF FCCu(1?à ¨â²70mm2)50?D?C
Product ID:90357
Updated: 2026/4/6

Key Features
- 1Handle short-circuits up to 65 kA at 220-240V AC. 2、Ensure reliable operation with a thermomagnetic release mechanism. 3、Build with a robust plastic case for extended durability. 4、Install easily using front terminal connections. 5、Meet IEC standards for safety and performance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Main Type | SACE Tmax T | Product Name | Moulded Case Circuit Breaker |
| Product Type | CB | Version | F |
| Electrical Durability | 8000 cycle 120 cycles per hour | Mechanical Durability | 25000 cycle 240 cycles per hour |
| Number of Poles | 4P | Power Loss | at Rated Operating Conditions per Pole 10,7 W |
| Rated Current (In) | 125 A | Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 800 V | Rated Operational Voltage | 690 V AC 500 V DC |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA | Rated Uninterrupted Current (Iu) | 160 A |
| Release | TMD | Release Type | TM |
| Short-Circuit Performance Level | N | Standards | IEC 60947 |
| Sub-type | T1 | Terminal Connection Type | Fixed Circuit-Breakers Front for Copper Cables |
| Test Voltage Max (Utest) | 3000 V | Manufacturer ID | 1SDA053387R1 |
Specifications may be subject to change without notice