T1N160 TMD32-500 4p F FC Cu(1?à¨′70mm2)50?D?C

Product ID:90350
Updated: 2026/4/6
ABB T1N160 TMD32-500 4p F FC Cu(1?à¨′70mm2)50?D?C

Key Features

  • 1Utilize durable materials for extended operational lifespan. 2、Employ a thermomagnetic trip unit with adjustable thermal protection. 3、Configure with four poles for versatile motor protection applications. 4、Simplify installation via front cable connection terminals. 5、Ensure compliance with international IEC safety standards.
Product Details
T1N160 TMD32-500 4p F FC Cu(1?à¨′70mm2)50?D?C
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 2,1 W
Rated Current (In)
32 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947
Sub-type
T1
Terminal Connection Type
Fixed Circuit-Breakers Front for Copper Cables
Test Voltage Max (Utest)
3000 V
Manufacturer ID
1SDA053381R1

Specifications may be subject to change without notice