T2H 160 MF12,5 Im=163A 3p F F

Product ID:70831
Updated: 2026/7/15
ABB T2H 160 MF12,5 Im=163A 3p F F

Key Features

  • 1Deliver reliable protection with a 163A short-circuit breaking capacity.
  • 2Ensure system uptime through durable industrial-grade construction.
  • 3Simplify integration with standardized front terminals and connections.
  • 4Reduce long-term costs with minimal maintenance requirements.
  • 5Receive orders fast with global shipping to 240+ countries.

Need price and lead time?

Request a quote for original ABB T2H 160 MF12,5 Im=163A 3p F F. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
1SDL000140R0
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Suitable For
T2
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1,1 W
Rated Current (In)
12.5 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA (230 V AC) 100 kA (380 V AC) 70 kA (400 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 55 kA (500 V AC) 36 kA (690 V AC) 8 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 10 kA (230 V AC) 10 kA (380 V AC) 70 kA (400 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 55 kA (500 V AC) 36 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 70 kA (250 V DC) 3 Poles in Series 85 kA (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
MF
Release Type
M
Short-Circuit Performance Level
H
Standards
IEC 60947
Sub-type
T2
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3000 V
Test Voltage at Industrial Frequency for 1 Minute
3000 V
Object Classification Code
Q
UNSPSC
39121100
Manufacturer ID
1SDA053142R1

Specifications may be subject to change without notice

Still deciding on T2H 160 MF12,5 Im=163A 3p F F?

Our engineers can confirm stock, price, and lead time for this ABB part.

Get a no-obligation quote in 1 minute.

Chat with us