T2H 160 MF2 Im=26A 3p F F

Product ID:90641
Updated: 2026/4/6
ABB T2H 160 MF2 Im=26A 3p F F

Key Features

  • 1Ensure reliable operation in demanding TMax XT systems. 2、Withstand 120 cycles per hour for 8000-cycle electrical durability. 3、Support up to 2A rated current for versatile applications. 4、Meet IEC standards with high insulation and operational voltage. 5、Achieve versatile compatibility with multiple voltage settings.
Product Details
T2H 160 MF2 Im=26A 3p F F
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
1SDL000140R0
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.1 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Suitable For
T2
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 2,5 W
Rated Current (In)
2 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA (230 V AC) 100 kA (380 V AC) 70 kA (400 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 55 kA (500 V AC) 36 kA (690 V AC) 8 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 10 kA (230 V AC) 10 kA (380 V AC) 70 kA (400 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 55 kA (500 V AC) 36 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 70 kA (250 V DC) 3 Poles in Series 85 kA (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
MF
Release Type
M
Short-Circuit Performance Level
H
Standards
IEC 60947
Sub-type
T2
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3000 V
Object Classification Code
Q
UNSPSC
39121100
Manufacturer ID
1SDA053134R1

Specifications may be subject to change without notice