T4L 250 MA 52-728 3p F F
Product ID:75804
Updated: 2026/4/11

Key Features
- 1Handle 52A current for efficient power distribution. 2、Customize fault levels with the MA trip unit. 3、Ensure reliability with 120kA fault level and 415V AC rating. 4、Simplify setup with easy front terminal installation. 5、Achieve up to 20,000 mechanical and 8,000 electrical cycles.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1057 | Product Net Width | 105 mm |
| Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 2.35 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T4 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 8000 cycle 120 cycles per hour |
| Mechanical Durability | 20000 cycle 240 cycles per hour | Number of Poles | 3 |
| Power Loss | at Rated Operating Conditions per Pole 3.9 W | Rated Current (In) | 52 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V) 70 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 120 kA (400 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 85 kA (690 V AC) 70 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 70 kA (750 V DC) 3 Poles in Series 50 kA | Rated Uninterrupted Current (Iu) | 250 A |
| Release | MA | Release Type | M |
| Short-Circuit Performance Level | L | Standards | IEC |
| Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front |
| Test Voltage Max (Utest) | 3500 V | Test Voltage at Industrial Frequency for 1 Minute | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39121100 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA055076R1 |
Specifications may be subject to change without notice
