T4L 250 UL/CSA TMA 200-1000..2000 3p F F
Product ID:87828
Updated: 2026/4/8

Key Features
- 1Utilize thermal-magnetic release for reliable operation across diverse conditions. 2、Handle short-circuit currents up to 200 kA at 220-230V AC for robust protection. 3、Meet stringent UL/CSA safety standards for North American market compliance. 4、Operate effectively across a wide voltage range from 220V to 690V AC. 5、Design with oversized and double insulation for enhanced safety and longevity.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Product Net Weight | 1 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | CB |
| Version | F | Mechanical Durability | 20000 cycle |
| Number of Poles | 3P | Power Loss | at Rated Operating Conditions per Pole 9.9 W |
| Rated Current (In) | 200 A | Rated Operational Voltage | 600 V AC 600 V DC |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 65 kA (500 V DC) 2 Poles in Series 65 kA (600 V DC) 3 Poles in Series 50 kA | Rated Uninterrupted Current (Iu) | 250 A |
| Release | TMA | Release Type | TM |
| Short-Circuit Performance Level | L | Standards | UL 489 CSA C22.2 |
| Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front |
| Test Voltage Max (Utest) | 3500 V | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Manufacturer ID | 1SDA058139R1 |