Key Features
- 1Withstand up to 85 kA short-circuit current for maximum safety. 2、Ensure durability with 20,000 operational cycles and robust construction. 3、Suit a wide range of industrial and commercial electrical systems. 4、Simplify installation with front terminal connections for quick setup. 5、Meet IEC 60947 standards for guaranteed performance and compliance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1057 | Product Net Width | 105 mm |
| Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 2.35 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T4 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 8000 cycle 120 cycles per hour |
| Mechanical Durability | 20000 cycle 240 cycles per hour | Number of Poles | 3 |
| Power Loss | at Rated Operating Conditions per Pole 3.9 W | Rated Current (In) | 52 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (690 V) 25 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA (230 V AC) 85 kA (380 V AC) 50 kA (400 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 40 kA (500 V AC) 30 kA (690 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 2 Poles in Series 36 kA (750 V DC) 3 Poles in Series 25 kA | Rated Uninterrupted Current (Iu) | 250 A |
| Release | MA | Release Type | M |
| Short-Circuit Performance Level | S | Standards | IEC |
| Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front |
| Test Voltage Max (Utest) | 3500 V | Test Voltage at Industrial Frequency for 1 Minute | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39121100 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA055073R1 |
Specifications may be subject to change without notice