T4V 250 TMA 250-2500 4p F F InN=100%In
Product ID:75696
Updated: 2026/4/10

Key Features
- 1Ensure reliable protection with a 250-2500A rated thermomagnetic circuit breaker. 2、Safeguard systems using a 4-pole configuration for enhanced control and flexibility. 3、Achieve 100% insulation integrity for superior safety in demanding applications. 4、Simplify installation with front terminals designed for copper cables. 5、Meet international IEC standards for performance and regulatory compliance.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1057 | Product Net Width | 140 mm |
| Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 3.05 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T4 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 8000 cycle 120 cycles per hour |
| Mechanical Durability | 20000 cycle 240 cycles per hour | Number of Poles | 4 |
| Power Loss | at Rated Operating Conditions per Pole 13.7 W | Rated Current (In) | 250 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC 750 V DC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V) 150 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V AC) 150 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 2 Poles in Series 70 kA | Rated Uninterrupted Current (Iu) | 250 A |
| Release | TMA | Release Type | TM |
| Short-Circuit Performance Level | V | Standards | IEC |
| Sub-type | T4 | Terminal Connection Type | Fixed Circuit-Breakers Front |
| Test Voltage Max (Utest) | 3500 V | Test Voltage at Industrial Frequency for 1 Minute | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
| UNSPSC | 39121100 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA054290R1 |
Specifications may be subject to change without notice