T5L400 PR222DS/P-LSIG In400 3pFFC1000VAC

Product ID:86434
Updated: 2026/7/21
ABB T5L400 PR222DS/P-LSIG In400 3pFFC1000VAC

Key Features

  • 1Deliver 400 A rated current for robust power distribution systems.
  • 2Ensure reliable protection with advanced solid-state release technology.
  • 3Simplify installation using front terminals compatible with copper cables.
  • 4Withstand 7000 electrical and 20000 mechanical cycles for durability.
  • 5Meet EU RoHS and REACH directives for environmental compliance.

Need price and lead time?

Request a quote for original ABB T5L400 PR222DS/P-LSIG In400 3pFFC1000VAC. Tell us your required quantity.

It only takes 1 minute — get your quotation and delivery time.
Quote within 24h
100% Original ABB
Global Delivery
No Spam · Secure

Need a quote? Enter your quantity and get pricing fast.

Qty

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK10103A1056 9AKK108467A6707
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
5.1 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
7000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 16.5 W
Rated Current (In)
400 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1150 V
Rated Operational Voltage
1000 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(1000 V AC) 10 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(1000 V AC) 12 kA
Rated Uninterrupted Current (Iu)
400 A
Release
PR222DS/P-LSIG
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers Front for Copper Cables
Test Voltage Max (Utest)
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA054538R1

Specifications may be subject to change without notice

Still deciding on T5L400 PR222DS/P-LSIG In400 3pFFC1000VAC?

Our engineers can confirm stock, price, and lead time for this ABB part.

Get a no-obligation quote in 1 minute.

Chat with us