T5L 600 UL/CSA BREAKING PART 3p F F

Product ID:74780
Updated: 2026/4/9
ABB T5L 600 UL/CSA BREAKING PART 3p F F

Key Features

  • 1Achieve high interrupting ratings up to 65 kAIC at 600 VAC. 2、Utilize advanced electronic trip units for precise protection. 3、Ensure compliance with UL 489 and CSA 22.2 standards. 4、Install easily with a compact, space-saving design. 5、Enhance functionality with versatile accessory options.
Product Details
T5L 600 UL/CSA BREAKING PART 3p F F
ABB

Technical Specifications

Detailed engineering parameters

ParameterValueParameterValue
Environmental Information
9AKK108467A6707
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
3.25 kg
Product Main Type
SACE Tmax T
Product Name
Moulded Case Circuit Breaker
Product Type
Breaking Part
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
3
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
600 V AC 600 V DC
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 65 kA (500 V DC) 2 Poles in Series 65 kA (600 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
600 A
Short-Circuit Performance Level
L
Standards
UL
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 65 kA (500 V DC) 2 Poles in Series 65 kA (600 V DC) 3 Poles in Series 50 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA061859R1

Specifications may be subject to change without notice