T5N 400 PR222DS/P-LSIG In=320 3p F F
Product ID:74372
Updated: 2026/4/9

Key Features
- 1Ensure reliable protection with a solid-state release. 2、Achieve up to 7000 electrical cycles for longevity. 3、Meet international IEC safety and performance standards. 4、Minimize energy loss with an optimized design. 5、Withstand 20000 mechanical cycles for durability.
Technical Specifications
Detailed engineering parameters
| Parameter | Value | Parameter | Value |
|---|---|---|---|
| Environmental Information | 9AKK10103A1056 9AKK108467A6707 | Product Net Width | 140 mm |
| Product Net Height | 205 mm | Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 5.1 kg | Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
| Suitable For | T5 | Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F | Electrical Durability | 7000 cycle 60 cycles per hour |
| Mechanical Durability | 20000 cycle 120 cycles per hour | Number of Poles | 3 |
| Power Loss | at Rated Operating Conditions per Pole 10.6 W | Rated Current (In) | 320 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV | Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC | Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA |
| Rated Uninterrupted Current (Iu) | 400 A | Release | PR222DS/P-LSIG |
| Release Type | EL | Short-Circuit Performance Level | N |
| Standards | IEC | Sub-type | T5 |
| Terminal Connection Type | Fixed Circuit-Breakers Front | Test Voltage Max (Utest) | 3500 V |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q | UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
| Manufacturer ID | 1SDA054322R1 |
Specifications may be subject to change without notice